Data sheet 11/14-FO009-9
FL ballasts
Electronic fixed output
RFI
Tridonic ballasts are RFI protected in accordance with EN 55015. To operate the
luminaire correctly and to minimise RFI we recommend the following instruc-
tions:
Connection to the lamps of the “hot leads” must be kept as short as possible
(marked with *)
Mains leads should be kept apart from lamp leads (ideally 5–10 cm distance)
Do not run mains leads adjacent to the electronic ballast
Twist the lamp leads
Keep the distance of lamp leads from the metal work as large as possible
Ballast must be earthed, either over the terminal or over the mounting screw
of the ballast
Mains wiring to be twisted when through wiring
Keep the mains leads inside the luminaire as short as possible
Defective lamp
If a lamp is defective, the ballast switches off and goes into standby. There is an
automatic restart once the lamp has been changed.
Loosen wire through
twisting and pulling
Side fixing feature
Screw M4, screw head diameter 8–10 mm
8 – 9 mm
wire preparation:
0.5 – 0.75 mm²
IDC interface
solid wire with a cross section of 0.5 mm² according to the specification
from WAGO
Horizontal interface
solid wire with a cross section of 0.5–0.75 mm² according to the specification
from WAGO
solid wire with a cross section of 1.0 mm² with an insulation diameter up to
2.5 mm
strip 9 mm of insulation from the cables to ensure perfect operation of the
push terminals
Loosen wire through twisting and pulling
T8 lamp information
18 W
36 W
Installation instructions
Isolation and electric strength testing of luminaires
Electronic devices can be damaged by high voltage. This has to be considered
during the routine testing of the luminaires in production.
According to IEC 60598-1 Annex Q (informative only!) or ENEC 303-Annex A, each
luminaire should be submitted to an isolation test with 500 V
DC for 1 second. This
test voltage should be connected between the interconnected phase and neutral
terminals and the earth terminal.
The isolation resistance must be at least 2 MΩ.
As an alternative, IEC 60598-1 Annex Q describes a test of the electrical strength
with 1500 V
AC (or 1.414 x 1500 V DC). To avoid damage to the electronic devices this
test must not be conducted.
Additional information
Additional technical information at www.tridonic.com Technical Data
Guarantee conditions at www.tridonic.com Services
No warranty if device was opened.
Ballast Terminal Maximum capacitance allowed
Type Cold Hot Cold Hot
PC 1x... T8 PRO lp 13, 14 15, 16 200 pF 100 pF
PC 2x... T8 PRO lp/sl 11, 12, 13, 14 15, 16 200 pF 100 pF
PC 3/4x18 T8 PRO lp (3x18W) 9, 10, 11, 12, 13, 14 15, 16 200 pF 100 pF
PC 3/4x18 T8 PRO lp (4x18W) 6, 7, 9, 10, 11, 12, 13, 14 15, 16 200 pF 100 pF
Wiring advice
The lead length is dependant on the capacitance of the cable.
For safety reasons, the PC T8 PRO must only be earthed in the case of a safety class 1 luminaire.
Earthing is not required for the device to operate. Connection to earth reduces radio interference.
With standard solid wire 0.5/0.75 mm² the capa-
citance of the lead is 30–80 pF/m. This value is
influenced by the way the wiring is made.
keep lamp wires short
lamp connection with multi-lamp ballasts should
be made with symmetrical wiring
lamp leads marked with * should be separated as
much as possible from other lamp leads
To avoid the damage of the control gear, the wiring must be protected against short circuits to earth
(sharp edged metal parts, metal cable clips, louver, etc.)
TC-L lamp information
wattage length
55 W 535 mm